CHIPLIMA | |||
---|---|---|---|
1 | Name of the Power Station | - | CHIPLIMA POWER STATION |
2 | Type of Project | - | ROR |
3 | Type of Power House | - | Surface |
4 | Total Number of Units & their rated capacities (Original) in MW | - | 3 nos. – 24 MW each |
5 | Unit – wise data of commissioning (Original) and after R & M. | - | Original Date of Comm. Unit-I -15.07.1962, Unit- II-26.11.1962. Unit-III -01.02.1964. Date of Comm. after R, M & U Unit-I -29.07.1998 Unit- II- (01.05.2008) Unit- III- (21.01.2020) |
6 | Turbines | ||
(a) Name of the Manufacturer | - | Unit -I & II – JM Voith (Original), Unit –III- LMZ Unit – I & II – Renovated by BHEL Unit III Renovated by Voith Hydro Pvt. Ltd. | |
(b) Country of Manufacturer | - | Unit -I & II –Germany, Unit-III - Russia | |
(c ) Type | - | Kaplan (each) | |
(d ) Arrangement of Shaft | - | Vertical (each) | |
(e ) Output in MW | - | 25.4 (Max.) for unit 1 & 2 27.874 (Max.)for unit 3 |
|
(f ) Speed in RPM | - | 150 (each) | |
(g ) Runaway Speed | - | 368 RPM, 340 RPM ( Unit 3 ) | |
(h ) Rated Head | - | 74.5 ft. | |
(i ) Designed Head | - | 72 ft., 71.52 ft. ( Unit-3) | |
7 | Governing System | ||
a) Name of the Manufacturer & Type | - | Unit-I –Voith, VCG – 72, Electro – Hydraulic Gov Unit-II – EHG (UR), BHEL Unit – III – Voith Hydro |
|
8 | Generators | ||
a) Name of the Manufacturer | - | Unit-I&II- Hitachi, Unit-III - Voith Hydro | |
b) Country | - | Unit-I&II- Japan, Unit -III - India | |
c) Type | - | Semi umbrella, Vertical | |
d) Output (in MVA / MW) | - | 27/24.3 (each) | |
e) Power Factor | - | 0.91 (each) | |
e) Generator Voltage | - | 11 KV (each) | |
e) Arrangement of Bearings | - | 1. Thrust bearing. 2. Guide bearing (each) |
|
9 | Excitation System | ||
Manufacturer & Type | - | Unit-I & II-AVR SEE, BHEL, Unit-III– SEE, ABB |
|
10 | Generator Transformers: | ||
a) Name of the Manufacturer & Country | - | Unit-I & II- Metropolitan – Vickers, UK Unit-3 Transformer & Rectifiers , India | |
b) Capacity in MVA | - | 27 MVA (each ) 30 MVA (Unit 3) | |
c) Type | - | Core (each) | |
d) Provision of tap changer | - | Off Load (each) | |
e) Type of cooling | - | OFWF (each) | |
f) Voltage Ratio & Vector Group | - | 11/132KV (each), Yd11 | |
11 | Power House EOT Crane: | ||
a) Name of the Manufacturer & Country | - | Litostrocz, Yugoslavia | |
b) Capacity of main hook & Aux. Hook | - | 125 T (main), 25T (Aux.) | |
c) Number of Cranes | - | Two | |
12 | Penstock: | ||
a) Arrangement | - | Trapezoidal | |
b) Numbers | - | Three | |
c) Dia | - | 9.4 M (each) | |
13 | Tail Race: | ||
a) Type | - | Open Channel | |
b) Length | - | 1 KM |